What Is A Multi-Function Meter?

multi-function meter is an electronic instrument that measures multiple electrical parameters from a single point in a power system. Unlike traditional analog meters that show only voltage or current, this device simultaneously displays active power (kW), reactive power (kVAR), apparent power (kVA), power factor, frequency, harmonic distortion (THD), and energy consumption (kWh/kVARh). Most units connect via current transformers (CTs) and voltage transformers (PTs). Data can be read locally on an LCD or transmitted remotely through RS485 (Modbus) to a building management system (BMS) or SCADA.

Core Functions of a Multi-Function Meter

FungsiDeskripsi
Real-time Parameter MonitoringMeasures volts, amps, kW, kVAR, kVA, Hz, power factor on each phase. Updates every 1 second.
Energy MeasurementAccumulates imported/exported active and reactive energy. Supports tariff-based billing.
Harmonic AnalysisReports individual harmonics up to 31st order and total harmonic distortion (THD) for voltage and current.
Demand LoggingRecords peak demand (kW/kVAR) over programmable intervals (15, 30, 60 min).
Data LoggingStores min/max values with timestamps. Non-volatile memory retains data after power loss.
KomunikasiRS485 (Modbus RTU) standard. Optional Ethernet, Profibus, or MQTT for IoT integration.

Types of Multi-Function Meter We Offer

3-PHASE watt-METER

Three-phase Watt-hour Meters

Tabel Spesifikasi Teknis

This table helps engineers and procurement teams quickly match the right multi-function meter to their system requirements.

ParameterTypical Range / Value
Input Voltage80–300V AC (direct) / 0–600V via PT
Input Current5A / 1A (via CT)
Frekuensi45–65 Hz
Measurement AccuracyClass 0.5S (active energy), Class 1 (reactive)
Sampling Rate256 samples per cycle
Harmonic MeasurementUp to 31st order
DisplayBacklit LCD (128×64) or TFT (optional)
Suhu Operasi-20°C to +70°C
Power Supply90–270V AC/DC, <5VA
Communication Ports1x RS485 (Modbus), 1x pulse output (optional Ethernet)
KandangIP50 (panel mount) / IP65 (optional)

Aplikasi Industri

Where a Multi-Function Meter Provides Actionable Data
A power factor correction capacitor needs accurate feedback to work properly. A multi-function meter supplies that feedback — measuring kW, kVAR, THD, and PF at the point of connection. Below are typical installations where our meter helps verify capacitor switching results, detects harmonic issues before relay trips, and provides utility-grade data for energy audits.

Why Choose ZHIMING's Multi-Function Meter?

True RMS measurement

Uses 256 samples/cycle. Works accurately even with distorted waveforms from VFDs or rectifiers. No calibration drift over 2 years.

Simple retrofit

This multi-function meter fits standard 96×96 mm cutout. Pin-compatible with older analog meters and many digital models. Typical swap takes 20 minutes including CT wiring check.

Dual energy registers

Stores import and export separately. Useful for sites with on-site solar or cogeneration. No need for two separate meters.

Built-in harmonic alarm

This multi-function meter can set a THD threshold (e.g., 10%). Its relay output triggers if exceeded, preventing nuisance capacitor bank switching in polluted grids.

No battery needed

Retains logs and settings via EEPROM. Works for 10+ years without maintenance. Firmware upgrade via USB port (front access).

Local support

Free configuration software (no license) and Modbus address map provided. Zhiming engineers assist with integration within 48 hours.

Ada pertanyaan?
Kami Punya Jawabannya

Produsen kapasitor daya terkemuka dengan pengalaman lebih dari 25 tahun siap menjawab semua pertanyaan Anda-meliputi masalah terkait produk, pertanyaan bisnis, atau masalah terkait layanan.

Masih Ada Pertanyaan? Kami Siap Membantu

Tidak menemukan yang Anda cari?

Hubungi Kami Kapan Saja

8093446000

Not for billing accuracy (requires Class 0.2S). But for sub-metering and internal energy management, Class 0.5S is sufficient.

Yes. It needs 90–270V AC/DC. Terminals L/N are separate from measurement inputs. Power consumption is below 5VA.

Use three CTs (one per phase) and connect voltage directly (L1, L2, L3, N). The meter calculates neutral current indirectly.

Yes, on the LCD. Press the “H” button to cycle through odd harmonics (3rd, 5th, 7th, etc.) up to 31st. For full spectrum, use Modbus.

The meter will show negative kW on that phase. Easy fix by swapping CT wires (S1/S2) without reprogramming.